Browse the catalog ↗RACK POWER DISTRIBUTION
Rack PDUs for data centers, colocation and edge. Start with your load, compare capabilities across vendors, and put together the right configuration with Matrix Solutions.

START WHERE YOU ARE
You know the voltage, plug, outlet mix or part number.
Browse the catalog ↗Start with rack load, redundancy and the available facility input.
Start with capacity ↗Understand sizing, phase, outlet planning and intelligence tiers.
Read the engineering guide ↗START WITH CAPACITY
| Nominal input | Typical application | Approx. kW | Catalog |
|---|---|---|---|
| 120V · 20A · single-phase | Network closets | 1.9 | See PDUs ↗ |
| 208V · 30A · single-phase | Light-to-medium racks | 5.0 | See PDUs ↗ |
| 208V · 30A · three-phase | Enterprise racks | 8.6 | See PDUs ↗ |
| 208V · 60A · three-phase | Dense compute | 17.3 | See PDUs ↗ |
| 415V/240V · 30A · three-phase | High-density builds | 17.3 | See PDUs ↗ |
| 415V/240V · 60A · three-phase | High-density GPU racks | 34.5 | See PDUs ↗ |
Examples assume balanced three-phase loading where applicable. Use the manufacturer’s published continuous rating; do not derate it twice. Catalog filters match indexed specifications, which may be incomplete. Understand the calculation ↗
PICK THE CAPABILITIES
Power distribution
Compare capabilities ↗Local load display
Compare capabilities ↗Remote readings & alarms
Compare capabilities ↗Remote outlet control
Compare capabilities ↗Per-device measurements
Compare capabilities ↗Automatic input transfer
Compare capabilities ↗Automatic transfer is a separate capability; it does not imply monitoring or outlet control. Vendor labels vary. Decode the product families ↗
SIZE FOR THE FAILURE CASE
Each path in an A/B pair must support the full design load when the other fails. Two 8.6 kW PDUs support an 8.6 kW redundant rack, not a 17.2 kW one.
Understand A/B sizing ↗
LINES WE CARRY
PX intelligent PDUs: compare inlet monitoring, outlet metering and switching.
Browse Raritan PDUs ↗Compare Smart, Smart POPS, Switched and Switched POPS capabilities.
Browse Server Technology PDUs ↗eConnect families for rack power monitoring and control; check cabinet fit.
Browse Chatsworth PDUs ↗Explore basic, metered, monitored, switched and automatic-transfer options.
Browse CyberPower PDUs ↗Browse Tripp Lite rack PDU options within Eaton’s portfolio.
Browse Eaton / Tripp Lite PDUs ↗Explore rack PDUs and compare local, networked and outlet-level capabilities.
Browse APC (Schneider) PDUs ↗BUYING FROM MATRIX
Share your load, facility input, outlet requirements and timeline. We can help compare configurations, confirm lead times and prepare a project quote.
FREQUENTLY ASKED
At 80% continuous loading and power factor 1: about 2.9 kW at 120V single-phase, 5.0 kW at 208V single-phase, 8.6 kW at 208V three-phase, or 17.3 kW at 415V three-phase. Verify the exact PDU and circuit ratings.
Compare your design load with the circuits available at your facility. Balanced three-phase delivers about 1.73 times the apparent power of single-phase at the same line-to-line voltage and current.
Size each surviving path for the full design load. Normal load sharing does not remove the need to support the load when the other feed fails.
In this guide, metered means local readings; monitored adds remote visibility. Vendor names vary, so confirm the capabilities of the exact product.
Check the equipment connections and required current. C19 outlets accept C20 plugs and are commonly used for higher-current equipment; ratings depend on the listed product and region.
Many networked PDUs support environmental sensors. Confirm sensor compatibility, supported measurements and whether sensors are sold separately.