MATRIX ENGINEERING GUIDES

PDU Intelligence Tiers: A Cross-Vendor Decoder

Compare capabilities behind vendor family names, from local metering to outlet control and automatic transfer.

The problem

Rack PDUs can be compared using six useful capabilities. Every manufacturer names them differently, and two vendors can use the same word for different things. "Smart" means monitored at one vendor and switched at another. "Managed" sometimes includes outlet metering and sometimes doesn't.

When you're comparing across brands, ignore the marketing label and check the capability grid.

The six capabilities

#CapabilityWhat it actually gives you
1DistributionPower distribution; protection arrangements depend on the model.
2Local displayLocal readings; display details vary. Networking is a separate capability.
3Unit-level remote monitoringNetwork access to measurements and alarms. Confirm the measured points, protocols and optional sensors.
4Outlet-level meteringEnergy and current per outlet. Chargeback, per-device capacity planning.
5Outlet switchingRemote on/off per outlet, power sequencing, outlet lockout.
6Automatic transferTwo inputs, automatic failover. For single-corded gear that still needs A/B.

Generic tier names used in the main guide: Basic (1), Metered (1+2), Monitored (1–3), Metered-by-outlet (distribution and outlet measurements; other features vary), Switched (1–3, 5), Switched + metered-by-outlet (1–5), ATS (6, usually with 2–3 or 5).

Vendor decoder

VendorFamily / labelGeneric tierNotes
Server Technology (Legrand)BasicBasic
Server Technology (Legrand)MeteredMetered
Server Technology (Legrand)SmartMonitored"Smart" here means network-monitored, not switched
Server Technology (Legrand)Smart POPSMetered-by-outletPOPS = Per Outlet Power Sensing
Server Technology (Legrand)SwitchedSwitched
Server Technology (Legrand)Switched POPSSwitched + metered-by-outlet
Server Technology (Legrand)PRO2 / PRO3X / PRO4X(generation, not tier)Controller platform; check available capabilities for the specific generation
Server Technology (Legrand)HDOT / HDOT Cx(outlet tech, not tier)High-density outlets; Cx = combination C13/C19 outlet
CyberPowerBasicBasic
CyberPowerMeteredMetered
CyberPowerMonitoredMonitored
CyberPowerSwitchedSwitched
CyberPowerMetered-by-OutletMetered-by-outlet
CyberPowerSwitched Metered-by-OutletSwitched + metered-by-outlet
CyberPowerMetered ATS / Switched ATSATS
APC (Schneider)BasicBasic
APC (Schneider)MeteredMonitoredAPC "Metered" is networked, not just local display
APC (Schneider)Metered-by-OutletMetered-by-outlet
APC (Schneider)SwitchedSwitched
APC (Schneider)Switched Metered-by-OutletSwitched + metered-by-outlet
APC (Schneider)Rack ATSATS
EatonBasicBasic
EatonMetered InputMonitored
EatonMetered OutletMetered-by-outlet
EatonSwitchedSwitched
EatonManagedSwitched + metered-by-outlet
EatonRack ATSATS
Tripp Lite (Eaton)BasicBasic
Tripp Lite (Eaton)MeteredMeteredLocal display; some models add network
Tripp Lite (Eaton)MonitoredMonitored
Tripp Lite (Eaton)SwitchedSwitched
Tripp Lite (Eaton)Switched with per-outlet meteringSwitched + metered-by-outlet
Tripp Lite (Eaton)ATSATS
Vertiv (Geist)BasicBasic
Vertiv (Geist)Unit-level monitoredMonitored
Vertiv (Geist)Outlet-level monitoredMetered-by-outlet
Vertiv (Geist)Unit-level switchedSwitched
Vertiv (Geist)Outlet-level switchedSwitched + metered-by-outlet
Chatsworth (CPI eConnect)BasicBasic
Chatsworth (CPI eConnect)MonitoredMonitored
Chatsworth (CPI eConnect)Monitored ProMetered-by-outlet"Pro" = outlet metering
Chatsworth (CPI eConnect)SwitchedSwitched
Chatsworth (CPI eConnect)Switched ProSwitched + metered-by-outlet
Raritan (Legrand)PX Inline MeterInline network monitoringMeasures an upstream feed; not a local-only rack PDU tier
Raritan (Legrand)PX MeteredMonitored
Raritan (Legrand)PX Outlet MeteredMetered-by-outlet
Raritan (Legrand)PX SwitchedSwitched
Raritan (Legrand)PX Switched + Outlet MeteredSwitched + metered-by-outlet
Raritan (Legrand)Transfer SwitchATS

Things the tier name doesn't tell you

The tier tells you what the PDU can measure and control. It doesn't tell you:

  • Branch circuit protection layout — how outlets are grouped into breaker banks. Check the protection arrangement of each candidate.
  • Controller hot-swap — whether a failed network module can be replaced without dropping power.
  • Linking — whether an A/B pair can share one IP and one login.
  • Outlet technology — locking outlets, combination C13/C19, alternating-phase layout on three-phase units.
  • Security posture — SNMPv3, TLS, LDAP/RADIUS, firmware update cadence. Increasingly a procurement gate.
  • Generation — Server Tech PRO2 vs PRO4X, APC Gen 2 vs Gen 3. Same tier, very different controllers and lifecycle.

These are separate facets in the finder, not tier attributes.

Manufacturer references

Use this decoder as a starting point. Confirm the exact model and current data sheet; a family label does not establish every capability.

PRO4X specifications — Server Technology · PX specifications — Raritan · eConnect families — Chatsworth · PDU selection — Eaton