MATRIX ENGINEERING GUIDES

Rack PDU Feature Glossary

Understand the power, monitoring, control and physical features that shape a complete rack PDU specification.

Power input

FeatureWhat it isTiersVendor names / notes
Input voltage / phase120, 208, 240, or 415/240V; single- or three-phase (delta or wye).All
Input amperageDistinguish nominal input current from the permitted continuous current; use the published installation rating.All
Input plugNEMA, Hubbell CS, IEC 60309, or IEC C14/C20 inlet. Must match the facility receptacle.All
Universal / field-changeable inputOne PDU body accepts interchangeable single- or three-phase input cords. Reduces SKU count for the buyer.Monitored+Server Tech "Universal Input" (PRO4X); Raritan "Field-replaceable input"
Angled infeedInput cord exits at 45° for easier routing in tight rear channels.AnyServer Tech "45° Angled Infeed"
Cord entryTop or bottom exit for the input cord. Match to overhead busway vs. floor whip.All
Cord lengthTypically 6–10 ft; longer options for overhead feeds.All

Outlets

FeatureWhat it isTiersVendor names / notes
C13 count / C19 countNumber of each IEC outlet type.All
NEMA outlets5-15R, 5-20R, L6-30R for legacy or downstream feeds.All
Combination C13/C19One outlet accepts either C14 or C20 plug.AllServer Tech "HDOT Cx"; Raritan "Cx"; Vertiv "Combination outlet"; Eaton "C39" (universal); APC "Combination"
Locking outletsMechanical retention for the plug; prevents accidental disconnect.AllServer Tech "RamLock"; Vertiv "U-Lock"; Raritan "SecureLock"; CPI "low-profile locking" (works with standard cords); APC/Eaton/CyberPower "Locking"
High-retention outletsTighter-grip outlets that work with standard cords; a step below locking.AllServer Tech "High Retention" (PRO2); Legrand "P-Lock" compatible
High-density outletsCompact outlet layout fitting more C13/C19 in the same length.AllServer Tech "HDOT"; Raritan "High Density"
Alternating phasePhases interleaved on adjacent outlets for easy load balancing on three-phase units.All (3Ø)Server Tech "Alternating Phase"; Raritan, Vertiv "Alternating phase"; Eaton "Phase-alternating"; CPI "Phase-balance outlets"
Outlet LED indicatorsPer-outlet status light (on/off/alarm).Switched, outlet-meteredServer Tech "RGB LED"; Raritan "Outlet LED"
Color codingChassis color options to distinguish A/B feeds or circuits.AnyServer Tech (6 colors); CPI (Black / Glacier White, sold as A/B "Redundancy Pack"); Raritan; Vertiv; APC (limited)

Protection

FeatureWhat it isTiersVendor names / notes
Branch circuit protectionOutlet banks protected by breakers or fuses as specified for the exact PDU; verify bank and outlet ratings.All (>20A)
Breaker typeMagnetic-hydraulic breaker (resettable) vs. fuse (replaceable). Breakers preferred for serviceability.All (>20A)
Branch current monitoringReads current per bank and alarms before a breaker trips.Monitored+Server Tech; Raritan; APC
Trip forensicsRecords measurements around a trip to help investigate the cause; capabilities vary by model.Outlet-meteredServer Tech "Circuit Breaker Trip Forensics" (PRO4X); Raritan "Trip cause"
High-temperature ratingMaximum permitted ambient temperature at the stated operating conditions; check the exact model.AllCPI (65°C); Server Tech, Raritan (60°C); many others 45°C
Flame ratingOutlet material rated UL94 V-0.All

Monitoring

FeatureWhat it isTiersVendor names / notes
Local displayLCD/LED showing input current per phase.Metered+Server Tech "Multi-Color LCD"; Raritan "Display"
Auto-flip displayDisplay orientation rotates for top- or bottom-fed mounting.Metered+Server Tech; Raritan
Inlet meteringNetwork-reported input A/V/W/VA/PF/kWh.Monitored+Server Tech "PIPS"; APC "Metered"; Raritan "Inlet metering"
Outlet meteringPer-outlet A/V/W/VA/PF/kWh.Outlet-meteredServer Tech "POPS"; APC "Metered-by-Outlet"; Eaton "Metered Outlet"; Vertiv "Outlet-level"; Raritan "Outlet Metered"
Metering accuracyPublished measurement accuracy and conditions. Confirm any billing or regulatory requirements separately.Monitored+Server Tech "Billing-grade"; Raritan "±1%"; ISO/IEC 62053
Power qualityHarmonics, THD, sags/swells, crest factor, waveform capture.Monitored+ (select)Server Tech "Power Quality Measurements", "THD", "Waveform Capture" (PRO4X); Raritan "Power quality"
Environmental sensorsPort for temperature, humidity, door, leak, airflow sensors; usually daisy-chainable.Monitored+Server Tech "DX2 SmartSensors"; Raritan "SmartSensor"; APC "NetBotz"; Vertiv "GT3HD"; Eaton "EMP"

Control

FeatureWhat it isTiersVendor names / notes
Outlet switchingRemote on/off/reboot per outlet or group.SwitchedServer Tech "Outlet Control"; APC/Eaton/Raritan "Switched"
Power sequencingStaggered outlet power-on after an outage to avoid inrush.Switched
Outlet lockoutPrevents a switched outlet from being turned off (protects critical loads).Switched
Load sheddingAuto-off of low-priority outlets on UPS battery or high load.SwitchedAPC, Eaton, Raritan

Management & network

FeatureWhat it isTiersVendor names / notes
Network interface10/100 or Gigabit Ethernet.Monitored+
Dual network portsSecond port for redundancy or for cascading.Monitored+ (select)Server Tech "Dual Network"; Raritan; APC Gen 3
Linking / cascadingMultiple PDUs share one IP and one login. Counts vary (2–32).Monitored+Server Tech "Linking", "Star Multi-Linking"; Raritan "Cascading"; APC "Network Port Sharing"; Vertiv "Chaining"; CPI "Secure Array" (up to 48, with failover IP)
Hot-swappable controllerNetwork/management module replaceable without dropping outlet power.Monitored+Server Tech; Raritan; Vertiv; APC Gen 3
ProtocolsHTTP(S), SSH, SNMPv2c/v3, Syslog, SMTP, (S)FTP, Modbus, Redfish, REST API.Monitored+
AuthenticationLDAP(S), RADIUS, TACACS+, local; 802.1X on newer units.Monitored+
DCIM / BMS integrationOpen API or certified integration with DCIM platforms.Monitored+Server Tech "Interoperability"; Sunbird, Nlyte, etc.
USB configurationMass-configure from a USB stick; no console cable needed.Monitored+Server Tech "USB Mass Configuration"; Raritan "USB config"
Firmware lifecycleGeneration / platform and support status. Same tier ≠ same controller.Monitored+Server Tech PRO2 / PRO3X / PRO4X; APC Gen 2 / Gen 3; Raritan PX3 / PX4

Physical

FeatureWhat it isTiersVendor names / notes
Form factor0U vertical, 1U/2U horizontal.All
Length / height0U length must match cabinet (42U, 45U, 48U, 52U).AllCPI filters as "42U or higher" / "45U or higher"
Rated capacity (kW)Published usable power at the specified voltage, current and loading conditions; regional ratings may differ.AllCPI lists both, e.g. "6.1 (UL) / 7.7 (CE) kW"
A/B pair SKUTwo PDUs sold together for redundant feeds, often in two colors.AnyCPI "Redundancy Pack"
MountingButton mounts, toolless brackets, custom bracket provisions.AllServer Tech "Flexible Mounting"
Chassis width / depthAffects fit in the rear channel beside a second PDU and cable management.All

Trademark → generic mapping (quick reference)

Vendor termGeneric
POPSOutlet metering
PIPSInlet metering
HDOTHigh-density outlets
HDOT Cx / CxCombination C13/C19 outlets
RamLock, U-Lock, SecureLockLocking outlets
Smart (Server Tech)Monitored
Metered (APC)Monitored
Managed (Eaton)Switched + outlet-metered
Network Port Sharing (APC), Secure Array (CPI)Linking / cascading
Monitored Pro / Switched Pro (CPI)Outlet metering added
NetBotz, SmartSensor, EMP, GT3HDEnvironmental sensor ecosystem