Server Technology C1S10SA-2PBA2B4 Smart Primary PRO1 PIPS PDU 1U (10) HDOT Outlets

Server Technology

Regular Price $1,125.00
Discount Price: $945.00
Product Overview:

Smart Primary PRO1 PIPS PDU, 1U, (10) HDOT Outlets (6xC13 + 4xCx), Input Amp Meter, 208-240V 30A Input w/ IEC 60309 6hr, 3-Pin, Blue plug, 10 ft (3m) Input Cord

MFG#:
C1S10SA-2PBA2B4
Adding to cart… The item has been added

Description:

Smart Primary PRO1 PIPS PDU, 1U, (10) HDOT Outlets (6xC13 + 4xCx), Input Amp Meter, 208-240V 30A Input w/ IEC 60309 6hr, 3-Pin, Blue plug, 10 ft (3m) Input Cord, Circuit Breakers, (2) Temperature/Humidity Sensor Capable

Specifications:

Input s
Input Voltage (V): 208
Frequency 50/60 Hz
Input Plug: NEMA L6-30P
Input Current (A): 30
Input Current Rated (A): 24
Input Power Capacity (kW): 5.0
Output s
Connect or Rating
(6) x IEC 60320/C13 North AmericanRating: ≤ 12A @208V L-L (15A Peak)
(4) x Cx North AmericanRating: ≤ 16A @208V L-L (20A Peak)
The Cx outlet has superior cable retention. Moderate force is required when plugging in a C14 or C20 connector to fully seat the plug and to ensure
proper installation. An incorrectly installed plug will be loose and will not provide a reliable connection.

Key Features
HDOT Cx Outl et s
Cx is the future-ready UL tested hybrid of a C13 and C19 outlet
accommodating both C14 and C20 plugs.
Net work Mo nit o r i ng
Gain access to valuable data through connections including
HTTP(S), SSH, Telnet, SNMP, (S)FTP, SMTP, Syslog, LDAP(S),
RS-232 serial, and more.
Ho t - S wap Net work Card
Network access is ensured when power is lost to the Primary
unit with backup power provided by the Linked unit.
S t a r Mul ti - Li nki ng
PRO2 provides the ability to link up to four power circuits
using one IP address. Primary Expansion PDU provides backup
power to network card.
T empera t ure/Humi dit y Mo nit o r i ng
Primary and Expansion (select products) units each support
two external 10' (3m) T/H probes. Receive SNMP-based alerts
and email notifications.
IP Ac c es s , S ec ur it y & Co mmuni c a ti o ns
Web, SSH, Telnet, SNMPv2c & v3, RS-232 serial, 10/100 Base
T-Ethernet, LDAP(S), TACACS+, RADIUS, DHCP, & SMTP/email.
Aut o - Fl i p Current Di s pl a y
Easy-to-read LEDs display current per phase to help prevent
overloads and simplify three-phase load balancing in highdensity cabinets.
Per - Inl et Power Sensing
PIPS® (Per Inlet Power Sensing) Monitors Current Load (A),
Voltage (V), Power (W), Apparent Power (VA), Crest Factor,
Power Factor, & Energy per inlet.
Branc h Ci r c uit Pro t ec ti o n
This PDU meets the UL and IEC 62368-1 requirement for
branch circuit protection through UL 489 rated magnetichydraulic circuit breakers or UL 248 fuses.
Hi gh Ret enti o n Lo c ki ng Outl et s
PRO2 receptacles have high retention and are compatible with
P-Lock type power cords.
Hi gh T emperature Rating
This product has been tested and approved for safe and
reliable operation in 60 °C data center environments.
Color - Coded Opti ons
Select from six colors to designate PDU circuits in the data
center — black, white, red, green, blue, and yellow.