Server Technology C-12HEK211 Metered PDU 1U

Server Technology

Regular Price $367.00
Discount Price: $308.00
Product Overview:

Metered PDU, 1U, 12 IEC C13 Outlets, LED amp meter, 230V 32A input with IEC 60309 2P+G 6hr Red Connector, 3m (10ft) cord, Internally Fused

MFG#:
C-12HEK211
Adding to cart… The item has been added

Metered PDU - 7.3kW, C-12HEK211

Key Features

  •  
    AUTO-FLIP CURRENT DISPLAY
    Easy-to-read LEDs display current per phase to help prevent overloads and simplify three-phase load balancing in high-density cabinets.
  •  
    BRANCH CIRCUIT PROTECTION
    This PDU meets the UL and IEC 60950-1 requirement for branch circuit protection through use of UL489 rated magnetic-hydraulic circuit breakers or UL248 fuses.
  •  
    HIGH RETENTION LOCKING OUTLETS
    Receptacles have high retention and are compatible with P-Lock type power cords.
  •  
    HIGH TEMPERATURE RATING
    This product has been tested and approved for safe and reliable operation in 60 °C data center environments.

Description

The Server Technology® Metered PDU provides reliable power distribution with local LED input current monitoring, allowing IT personnel to determine safe levels of loading on a per-phase basis while installing equipment into the rack/cabinet.

Inputs

Input Voltage (V): 230
Input Plug: IEC 230V/32A 2P+PE 6Hr
Input Current (A): 32
Input Current Rated (A): 32
Input Power Capacity (kW): 7.3

Outputs

Connector Rating
(12) x IEC 60320/C13 Global Rating: ≤ 10A @230V L-N

Branch Circuit Protection

(2) 20A Fuses, two (2) branch, meets UL 60950-1 requirements (Bussmann SC-20 fuses), 100 kA Interrupt Rating

Physical

Dimensions: 1.75in tall x 17.2in wide x 5.0in deep [45mm x 437mm x 127mm]

Environmental

Operating Environment: 32°F to 140°F / 0°C to 60°C | 8%RH to 90%RH non-condensing | 6,500ft/2km elevation
Storage Environment: -40°F to 185°F / -40°C to 85°C | 8%RH to 90%RH non-condensing | 50,000ft/15km elevation
Quiescent / Unloaded Power Draw: < 10W for all configurations

Communications & Security

Not Applicable

Certifications

Global:
Safety
  • EN 62368-1 (TUVR certified, T-mark)
  • IEC 60950-1 incl. regional, national and harmonized differences (IECEE CB scheme)
  • IEC 62368-1 incl. regional, national and harmonized differences (IECEE CB scheme)

  • RoHS, European Hazardous Materials Directive, 2011/65/EU
  • WEEE Compliant
  • CE Mark
  • UK Legislation
  • RoHS, Electrical Equipment (Safety)

Measurement Accuracy

Input Measurement Accuracy:
LED Current = ± 10% at 0.1 amp (1.0 - 9.9 amps) and 1 amp (> 9.9 amps) resolution