PDU - Power Distribution Management
Overview
Rack PDUs from Raritan, Server Technology, APC, Vertiv and Eaton — basic, metered, monitored and switched, 15 A to 60 A, single- and three-phase, in 0U vertical and 1U/2U horizontal formats. Not sure which line fits your rack? Start with our rack PDU sizing guide or compare intelligence tiers across vendors.
Read moreRead less
Filter by input plug, voltage, outlet mix and monitoring level below, or contact us / call (800) 217-8085 with your rack layout and we’ll work through the spec with you. Over 5,000 PDUs, most shipping in 5–10 business days.
How to choose a rack PDU in five questions
- What circuit feeds the rack? Match the PDU’s input to the branch circuit exactly: voltage (120 V, 208 V, 240 V or 400/415 V), single- or three-phase, and breaker rating (15, 20, 30, 50 or 60 A). A 30 A three-phase 208 V feed delivers about 8.6 kW at the 80% continuous-load rating; a 60 A feed about 17.3 kW.
- Which plug? The input plug is set by the circuit — NEMA L5-20P/L5-30P for 120 V, L6-20P/L6-30P for 208/240 V single-phase, L21-30P or L15-30P for three-phase, and IEC 60309 pin-and-sleeve for 50/60 A and 400 V. Filter by input plug below and the wrong ones disappear.
- Which outlets, and how many? Count your equipment cords: C13 for most servers and switches, C19 for high-draw gear such as blade chassis and large storage. Locking outlets stop cords backing out. Choose a PDU with headroom for growth — outlet count is the spec you cannot change later.
- How much visibility do you need? Basic distributes power only. Metered adds a local display of input load so you never trip a breaker. Monitored puts that data on the network. Switched lets you remotely power-cycle individual outlets. Outlet-level metering shows draw per device. See our cross-vendor decoder of intelligence tiers.
- Where does it mount? 0U vertical PDUs mount in the rear of the cabinet and keep rack units free; 1U/2U horizontal units suit shallow or shared racks. Dual-feed (A/B) racks want two PDUs on separate circuits.
The full walkthrough — load calculation, redundancy and environmental sensors — is in the rack PDU sizing and engineering guide. Terms you meet along the way are defined in the PDU feature glossary.
Products
Showing 1 - 24 of 261

Tripp Lite
SINGLE-PHASE Metered Input Rack PDU G4, 230V, 4 C13 and 4 C39 Outlets, 16A, 3.7K EHMIL620N
MPN: EHMIL620N

Tripp Lite
SINGLE-PHASE Metered Input Rack PDU G4, 120V, 8 NEMA 5-15R Outlets, 12A, 1.4KW, EHMI515L
MPN: EHMI515L

Tripp Lite
UNIVERSAL-INPUT Metered Rack PDU G4, 200-415V, 18 C13 and 18 C39 Outlets, Input EHMIGU23D
MPN: EHMIGU23D
Power the rack. PDU Guide.
Rack PDUs for data centers, colocation and edge. Start with your load, compare capabilities across vendors, and build the right configuration.

Tripp Lite
UNIVERSAL-INPUT Managed Rack PDU G4, 200-415V, 18 C13 and 18 C39 Outlets, Input EHMAGU23D
MPN: EHMAGU23D

Tripp Lite
SINGLE-PHASE Managed Rack PDU G4, 208V, 10 C13 and 10 C39 Outlets, 24A, 5KW, L6- EHMAL630B
MPN: EHMAL630B

Tripp Lite
Eaton EPDU TPC4100-C 12-Outlets 8.64KW PDU TPC4100-C
MPN: TPC4100-C

Tripp Lite
Eaton PDU EPO 1U in: L5-30P 24A OUT: 6X5-15R, TPC2806-3747R
MPN: TPC2806-3747R

Tripp Lite
Eaton EPDU 10-Outlets PDU - TPC3225 - Power Distribution UNIT - 1U - 3 YEAR WARR TPC3225
MPN: TPC3225

Tripp Lite
Eaton Powerware EPDU TPC4100 12-Outlets 5.76KVA PDU TPC4100-A2
MPN: TPC4100-A2

Tripp Lite
Eaton EPDU, RE, 1U, C20, (12) C13 TPC2365-R
MPN: TPC2365-R

Tripp Lite
Eaton EPDU, BA, 1U, MIL, (6) 5-15R, (2) 5-20R TPC2806
MPN: TPC2806

Tripp Lite
Eaton REPO RACK PDU, 1U, 3.84 KW MAX, 100-240V, 16A, C20 Inlet, Single-Phase, TI TPC2365-Ltmtd-R
MPN: TPC2365-LTMTD-R

Tripp Lite
Eaton TPC2365 - Power Distribution UNIT - 1U - 110-125V - 3.33KW - 12-Outlets C1 TPC2365
MPN: TPC2365

Tripp Lite
Eaton Powerware EPDU TPC2234-a 8-Outlets 1.44KVA PDU TPC2234-a
MPN: TPC2234-A

Tripp Lite
Eaton EPDU TPC2234-a-F 8-Outlets 1.44KW PDU TPC2234-a-F
MPN: TPC2234-A-F

Tripp Lite
Eaton Powerware EPDU TPC2105-2-107 10-Outlets 5.76KVA PDU TPC2105-2-107
MPN: TPC2105-2-107

Tripp Lite
Eaton Powerware EPDU TPC2105-1-119 16-Outlets 5.76KVA PDU TPC2105-1-119
MPN: TPC2105-1-119

Tripp Lite
TPC2105-2 - Power Distribution UNIT - RACK-Mountable,1U - 110-125V, 208-240V - 3 TPC2105-2
MPN: TPC2105-2

Tripp Lite
Eaton Powerware EPDU 12-Outlets 1.44KVA PDU TPC12F-a-CB
MPN: TPC12F-A-CB

Tripp Lite
Eaton Basic RACK PDU, 1U, Hardwired Input, 3.33 KW MAX, 110-125V, 208-240V, 24A, TPC2105-1
MPN: TPC2105-1

Tripp Lite
Eaton Power Distribution UNIT - RACK-Mountable - AC 120 V - 12 X Power NEMA 5-15 TPC12-a-RCB
MPN: TPC12-A-RCB

Tripp Lite
Eaton Powerware EASY Basic RACK TPC12-a-CB 12-Outlets PDU TPC12-a-CB
MPN: TPC12-A-CB

Tripp Lite
Eaton EPDU, RE, 1U, L5-30P, (10) 5-20R TPC115-10D-R
MPN: TPC115-10D-R

Tripp Lite
Eaton TPC115-3538 Power Distribution UNIT - 1U - 110-125V - 1.92KW - 16A TPC115-3538
MPN: TPC115-3538
Showing 1 - 24 of 261