-48 VDC PDU - 9.6kW, 48DCWC-16-2X100-A0
Key Features
-
NETWORK MONITORINGGain access to valuable data through connections including HTTP(S), SSH, Telnet, SNMP, (S)FTP, SMTP, Syslog, LDAP(S), RS-232 serial, and more.
-
HOT-SWAP NETWORK CARDNetwork access is ensured when power is lost to the Primary unit with backup power provided by the primary link unit.
-
STAR MULTI-LINKINGProvides the ability to link up to four power circuits using one IP address. Primary link provides backup power to network card.
-
TEMPERATURE/HUMIDITY MONITORINGPrimary and Link units each support two external 10' (3m) T/H probes. Receive SNMP-based alerts and email notifications.
-
OUTLET CONTROLOn Switched rack PDUs, cycle power to individual outlets or groups of outlets to reboot servers. Or, power off unused receptacles.
Description
No description available.Inputs
Input Voltage (V): | -48 |
Input Current (A): | 200 |
Input Current Rated (A): | 200 |
Input Power Capacity (kW): | 9.6 |
Outputs
Terminals: (16) x Screw-down terminals (10A max)Branch Circuit Protection
GMT Fuses IncludedPhysical
Dimensions: 3.5in tall x 17.0in wide x 12.0in deep [89mm x 432mm x 305mm]Environmental
Operating Environment: 32°F to 122°F / 0°C to 50°C | 8%RH to 90%RH non-condensing | 6,500ft/2km elevationStorage Environment: -40°F to 185°F / -40°C to 85°C | 8%RH to 90%RH non-condensing | 50,000ft/15km elevation
Quiescent / Unloaded Power Draw: < 10W for all configurations
Communications & Security
10/100/1000 Mbps Ethernet (RJ-45 connector), RS-232 serial (RJ-45 connector)Two (2) temperature/humidity sensor inputs (4P4C), Link port (RJ-12) - {also on Link PDU}
Web-browser GUI and command-line interface (CLI): HTTP/HTTPS, TLSv1.2, SSHv2, Telnet, SNMPv2c and v3 (GET, SET, Traps), IPv4 and IPv6, LDAPv3/LDAPS, TACACS+, RADIUS, FTP/SFTP
Certifications
North American:Safety (TUVR certified, cTUVus mark)
- UL Std. 60950-1, 62368-1
- CAN/CSA-C22.2 No. 60950-1, CAN/CSA-C22.2 No. 62368-1
- FCC Part 15 Subpart B Sections 15.107 & 15.109, Class A
- CAN ICES-003, Class A
Global:
Safety
- EN 62368-1 (TUVR certified, T-mark)
- IEC 60950-1 incl. regional, national and harmonized differences (IECEE CB scheme)
- IEC 62368-1 incl. regional, national and harmonized differences (IECEE CB scheme)
- EN 55032 / IEC 55032 / CISPR 32
- EN 55024 / CISPR 24
- EN 55035 / IEC 55035 / CISPR 35
- EN 61000-3-2 / IEC 61000-3-2
- EN 61000-3-3 / IEC 61000-3-3
- RoHS, European Hazardous Materials Directive, 2011/65/EU
- WEEE Compliant
- CE Mark
- UK Legislation
- RoHS, Electrical Equipment (Safety) and Electromagnetic Compatibility
Measurement Accuracy
Input Measurement Accuracy:LED Current = ± 10% at 0.1 amp (0.5 - 9.9 amps) and 1 amp (> 9.9 amps) resolution
GUI Current = ± 5% at 0.01 amp resolution (above 0.5 amp)