Description:
Switched POPS PRO2, PIPS (Per Input Power Sensing), 0U, 18 x IEC C13 & 6 x IEC C19 Outlets, 3 x LED Amp Meters, 240/415V 3-phase Wye 30A, NEMA L22-30P Plug, 10ft (3m) Cord, Top Power Cord Entry, Middle Display/Network, 2 x Temp/Humidity Capable, Circuit Breakers
Network Monitoring
- Gain access to valuable data through connections including HTTP(S), SSH, Telnet, SNMP, (S)FTP, SMTP, Syslog, LDAP(S), RS-232 serial, and more.
Hot-Swap Network Card
- Network access is ensured when power is lost to the Master unit with backup power provided by the primary link unit.
Star Multi-Linking
- Provides the ability to link up to four power circuits using one IP address. Primary link provides backup power to network card.
Temperature/Humidity Monitoring
- Master and Link units each support two external 10' (3m) T/H probes. Receive SNMP-based alerts and email notifications.
Auto-Flip Current Display
- Easy-to-read LEDs display current per phase to help prevent overloads and simplify three-phase load balancing in high-density cabinets. "Switched POPS"
Specifications For The STV-6543Z:
Inputs | |
---|---|
Input Voltage (V) | 415 |
Input Plug | NEMA L22-30P |
Input Current (A) | 30 |
Input Current Rated (A) | 24 |
Input Power Capacity (kW) | 17.3 |
Outputs | |
(18) x IEC 60320/C13 | North American Rating: ≤ 12A @240V L-N (15A Peak) |
(6) x IEC 60320/C19 | North American Rating: ≤ 16A @240V L-N (20A Peak) |
Branch Circuit Protection | |
UL489 Compliant 1-pole, 20A trip circuit breakers, six (6) branch, rating: ≤ 16A, 10 kAIC Interrupt Rating
|
|
Physical | |
|
|
Environmental | |
Operating Environment | 32°F to 140°F / 0°C to 60°C | 8%RH to 90%RH non-condensing | 6,500ft/2km elevation |
Storage Environment | -40°F to 185°F / -40°C to 85°C | 8%RH to 90%RH non-condensing | 50,000ft/15km elevation |
Communications & Security | |
Two (2) temperature/humidity sensor inputs (4P4C), Link port (RJ-12) - {also on Link PDU} Web-browser GUI and command-line interface (CLI): HTTP/HTTPS, TLSv1.2, SSHv2, Telnet, SNMPv2c and v3 (GET, SET, Traps), IPv4 and IPv6, LDAPv3/LDAPS, TACACS+, RADIUS, FTP/SFTP |
|
Certifications | |
North American :
cTUVus Mark to UL 60950-1:2007 R10.14 CAN/CSA-C22.2 No. 60950-1-07+A1:2011+A2:2014 FCC Part 15 Subpart B Sections 15.107 and 15.109, Class A |
|
Measurement Accuracy | |
Input Measurement Accuracy | LED Current = ± 10% at 0.1 amp (0.3 - 9.9 amps) and 1 amp (> 9.9 amps) resolution |
Output Measurement Accuracy | GUI Current = ± 1% at 0.01 amp resolution (above 0.15 amp) |
Branch Measurement Accuracy | Current = ± 3% at 0.01 amp resolution (above 0.5 amp) |
Optional Accessories | |
EMTH-1-1 Combination Temperature/Humidity Probe, 10ft (3m)
EMCU-1-1B Environmental Monitor adding: - Two (2) EMTH-1-1 temperature/humidity ports (one probe included) - One (1) EMWS-1-1 water sensor port (probe sold separately) - Four (4) dry contact (NO/NC) monitoring points - One (1) 8-bit analog-to-digital converter (0 to 5VDC) KIT-PRO2LINK-01M or -01D provides ability to link (2) additional PRO2 units KIT-SUS-01 StartUp Stick™ for rapid configurationMounting Brackets - Buttons (KIT-0020) included for tool-less mounting (see diagram) - See the Mounting Bracket Guide for further suggestions - Custom mounting options available. Contact your local Server Technology representative Cable Retention Devices for non-locking cords - EZip - Cable Sleeve |
|
Additional Information | |
Warranty | Server Technology offers a standard 2-year limited parts & labor warranty. Extended support is available at the time of purchase. |